Chapter 12 RPV Tools
RPV311
RPV311-TM-EN-6
206
Example of a configuration file with RPV:
Below is the configuration of the xml file with an interval of 300 seconds between the cycles.
First RPV: activated scanning, RPV 192.168.0.195, waiting time for connection of 60 seconds, scanning
fault, disturbance, steady state and SOE records, no baud rate limit, automatic deletion of records, activated
modem, telephone number for connection to the modem 21080 300;
Second RPV: activated scanning, RPV 192.168.0.199, waiting time for connection of 60 seconds, scanning
fault records, no baud rate limit, automatic deletion of records, no modem.
?xml version="1.0" encoding="UTF-8"?
scanner
interval300interval
list
equipment enabled="yes
address192.168.0.195address
timeout60timeout
records
recordfault/record
recorddisturbancerecord
recordsteadystaterecord
recordsoerecord
records
bandwidth0bandwidth
deleteyesdelete
modem enabled="yes"
phonenumber21080300phonenumber
modem
equipment
equipment enabled="yes"
address192.168.0.199address
timeout60timeout
records
recordfaultrecord
records