RPV311
Chapter 17 Technical Specifications
RPV311-TM-EN-6
316
2.9 ENVIRONMENTAL CONDITIONS
Environmental Conditions
Operating temperature range
- 40… +50 °C (or 13°F to +122°F)
Maximum operating altitude
2000 m (6560 ft)
Relative humidity
5 … 95 %, noncondensing
As tested per 60068-2-1
-40°C
As tested per 60068-2-2
+55°C
2.10 TYPE TESTS RPV311
Type Tests RPV311
IEC 61000-4-2:2008
8kV contact / 15KV air (level 4)
IEC 61000-4-3:2006
10 V/m
IEC 61000-4-4:2012
2 KV @ 5KHz (level 3)
IEC 61000-4-5:2005
Differential mode: 1KV
Common mode: 2KV
(level 3)
IEC 61000-4-6:2008
10V
IEC 61000-4-8:2009
30A/m continuous - 300A/m @ 1s.