RPV311
Chapter 17 Technical Specifications
RPV311-TM-EN-6
318
Gradual Startup
Shut-down ramp: 60s
Power off: 5m
Start-up ramp: 60s
CISPR11:2009
Radiated emission
Limits:
30 to 230MHz - 50dB(μV/m) quasi peak at 3m
230 to 1000MHz - 57dB(μV/m) quasi peak at 3m
CISPR22:2008
Radiated emission
Limits:
1 to 3GHz - 56dB(μV/m) average; 76dB(μV/m) peak at 3m
3 to 6GHz - 60dB(μV/m) average; 80dB(μV/m) peak at 3m
The test frequency is defined based on the maximum internal frequency of
equipment.
Conducted emission
Limits:
0.15 to 0.50MHZ - 79dB(μV) quasi peak; 66dB(μV) average
0.5 to 30MHz - 73dB(μV) quasi peak; 60dB(μV) average
2.11 SAFETY TESTS
Safety tests
Safety
IEC 61010-1
IEC 60255-5
Inpulse - 5KV
Dielectric withstand - 3,3KVDC for 60 seconds
Insulation > 100M Ω