EasyManua.ls Logo

Alstom Reason RPV311 - DC Transducer Inputs Specifications; Digital Inputs Specifications

Alstom Reason RPV311
350 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 17 Technical Specifications
RPV311
RPV311-TM-EN-6
323
3.6 DC TRANSDUCER INPUTS
DC Transducer inputs specifications
Full Scale
± 10 V
± 20 mA
Input range
- 10 to + 10 V
- 20 to 20 mA
Analog Input Accuracy
± 0.1 % of FS magnitude
range
± 1 % of FS magnitude
range
Impedance
> 5 kΩ
10 Ω
3.7 DIGITAL INPUTS
Digital Inputs specifications
Nominal Voltage
125 V
250 V
24 / 48 V
Level Low
40 V
75 V
08 V
Level High
85 V
160 V
17 V
Impedance
82 kΩ
160 kΩ
15 kΩ
Burden
< 0.25 W
< 0.5 W
< 0.2 W
Continuous Overload ¹
240 V
340 V
100 V
The digital inputs are protected against continuous reverse polarity for the nominal voltage

Table of Contents