SERVICING
55
LIQUID PRESSURE
AT SERVICE VALVE (PSIG) 8 10 12 14 16 18
189
58 56 54 52 50 48
195
60
58
56
54
52
50
202 62 60 58 56 54 52
208
64
62
60
58
56
54
215 66 64 62 60 58 56
222
68
66
64
62
60
58
229 70 68 66 64 62 60
236
72
70
68
66
64
62
243
74 72 70 68 66 64
251 76 74 72 70 68 66
259
78
76
74
72
70
68
266
80
78
76
74
72
70
274
82
80
78
76
74
72
283
84
82
80
78
76
74
291
86
84
82
80
78
76
299
88
86
84 82 80 78
308
90
88
86
84
82
80
317
92 90 88 86 84 82
326
94
92
90
88
86
84
335
96
94
92
90
88
86
345
98
96
94
92
90
88
354
100
98
96
94
92
90
364
102
100
98
96
94 92
374
104
102
100
98
96
94
384
106
104 102 100 98 96
395
108
106
104
102
100
98
406 110 108 106 104 102 100
416
112
110
108
106
104
102
427 114 112 110 108 106 104
439
116
114
112
110
108
106
450 118 116 114 112 110 108
462
120
118
116
114
112 110
474 122 120 118 116 114 112
486 124 122 120 118 116 114
499
126
124
122
120
118
116
511 128 126 124 122 120 118
REQUIRED SUBCOOLING TEMPERATURE (°F)
REQUIRED LIQUID LINE TEMPERATURE