Summary

Operation

Remote Programmer Keys

Details the four keys on the remote programmer: Enter, Cancel, Scroll Up, and Scroll Down.

Setting Detection Distance

Procedure for Setting Detection Distance

Explains the steps to set the detection distance by interacting with the sensor using the programmer.

Programmer Menu Functions

Cleaning Mode Functionality

Disables the sensor for one minute to facilitate cleaning of the fixture or fitting.

Disinfection Mode Functionality

Used in healthcare facilities for high-temperature or anti-bacterial purging of water lines.

Diagnostics Mode Functionality

Allows determination of faucet or flush valve settings, compatible with products manufactured from 2008.

Parameter, Language, and Backlight Settings

Parameter Settings Overview

Guides users through menu options to configure various device parameters.

Language Selection Options

Enables users to choose the display language for the programmer interface.

Backlight Intensity Adjustment

Allows adjustment of the display's backlight for optimal viewing in different lighting conditions.

Hand-Wash Faucet Mode Configuration

Comfort Timeout for Hand-Wash

Sets how long water runs after hands are removed from the detection zone. Recommended 1.5 sec.

Safety Timeout for Hand-Wash

Prevents continuous water flow if sensor is blocked. Recommended 55 sec.

Auto-Rinse for Hand-Wash

Automatically flushes faucet after non-use to prevent stagnant water. Adjustable duration.

Sensor Distance for Hand-Wash

Sets the maximum detection range for Hand-Wash faucets. Recommended 16 cm.

Metering Faucet Mode Configuration

Comfort Timeout for Metering Faucet

Sets the run time for water flow when activated by the user in Metering mode.

Auto-Rinse for Metering Faucet

Enables automatic flush after non-use to prevent stagnant water. Default setting is OFF.

Sensor Distance for Metering Faucet

Sets the maximum detection range for Metering faucets. Recommended 16 cm.

Metering with On/Off Faucet Mode

Comfort Timeout for On/Off Metering

Sets run time; user starts/stops flow. Suited for gooseneck fittings with short detection.

Sensor Distance for On/Off Metering

Sets a short detection range for on/off functionality. Recommended 5 cm.

Urinal Flush Valve Settings

Urinal Detection Interval

Time user must be in zone to arm flush valve. Eliminates false flushing. Recommended 5 sec.

Urinal Rinse Start Interval

Time after user leaves zone before valve flushes. Recommended 2 sec.

Urinal Heavy Flush Settings

Configures large water delivery after pre-programmed flushes or time to prevent drain clogging.

Urinal Stadium Mode

Automatically switches to flush every 2 minutes during heavy usage periods.

Urinal Sensor Distance

Sets the maximum detection distance for urinal sensors. Recommended 40 cm.

Flushometer Toilet Flush Valve Settings

Flushometer Detection Interval

Time user must be in zone to arm flush valve. Eliminates false flushing. Recommended 5 sec.

Flushometer Rinse Start Interval

Time after user leaves zone before valve flushes. Recommended 2 sec.

Flushometer Sensor Distance

Sets the maximum detection distance for toilet flush valves. Recommended 60 cm.

Dual Flush Toilet Flush Valve Settings

Dual Flush Short Rinsing

Sets flush time for users in detection zone for less than 1 minute.

Dual Flush Detection Interval

Time user must be in zone to arm flush valve. Recommended 5 sec.

Dual Flush Rinse Start Interval

Time after user leaves zone before valve flushes. Recommended 2 sec.

Dual Flush Sensor Distance

Sets the maximum detection distance for toilet flush valves. Recommended 60 cm.