5.0 STORAGE AND MAINTENANCE
Operation
The UPS system contains no user-serviceable parts. If the battery
service life (3~5 years at 25°C ambient temperature) has been
exceeded, the batteries must be replaced. In this case, please
contact your dealer.
Be sure to deliver the spent battery to a recycling
facility or ship it to your dealer in the replacement
battery packing material.
Storage
Before storing, charge the UPS 5 hours. Store the UPS covered
and upright in a cool, dry location. During storage, recharge the
battery in accordance with the following table:
Storage Temperature Recharge Frequency Charging Duration
-25°C - 40°C Every 3 months 1-2 hours
40°C - 45°C Every 2 months 1-2 hours