3.11 Strapping Table (Continued)
Figure 3-15
Menu Screen Transforms to
Strapping Table
Table 3-2
Universal III
Strapping Table
Point Number Level Standard Level Optional Output Value
Preset Values Values In Selected
% Level % Level Units
1. 0
2. 5
3. 10
4. 15
5. 20
6. 25
7. 30
8. 35
9. 40
10. 45
11. 50
12. 55
13. 60
14. 65
15. 70
16. 75
17. 80
18. 85
19. 90
20. 95
21. 100
By clicking on Last Read
Values, this view may also be
used to review existing strapping
tables previously entered.
A. Plan your table by lling out table 3-2. You may use the
rst column which lists every 5% between 0 and 100%,
or you may ll in your own values in column 2.
B. Fill out column 3 with output values corresponding to
those listed in column 1 or 2.
C. "Click" on
Strapping Table button to access table:
D. Enter the values you calculated into the screen view
presented.
E. "Click" on
Write Strapping Table.
F. "Click" on
Exit when completed.