509-7X Series Universal III™ Transmitter
38
Figure 3-20
Typical Printout of Transmitter Data
AMETEK Drexelbrook
205 Keith Valley Road
Horsham, PA 19044
Telephone: 215-674-1234
FAX: 215-674-2731
Service: 800-527-6297
Tag-ID: LT 101 Serial Number: 1172
Scratch PAD: 1000 pf NPO validation capacitor Software Version: 3.1
Analog Loop Assign: LEVEL Range Position: 4
Damping Time: 0 sec. Type: 30
Level Configuration Vessel Configuration Level Calibration
Level Units: feet Vessel Units: gallons Lower Level: 0 ft
Maximum Level: 10.00 ft Maximum Capacity: 1200.00 gal Upper Level: 10 ft
Level Type: Standard Vessel Type: Vertical Lower Capacitance: 50 pf
Upper Capacitance: 2000 pf
LRV (4mA): 0.00 ft
URV (20 mA): 10.00ft
Real Time View
Level: 10 ft
Vessel: 600 gal
Capacitance: 1000 pF
Loop Current: 12.00 mA
Percentage: 50 %
Status: OK
Strapping Table
Vessel Type: Vertical
Number of Points: 21
Level Volume
In Percent Out Percent
0.00 0.00 o.oo 0.00
1.00 5.00 60.00 5.00
2.00 10.00 120.00 10.00
3.00 15.00 180.00 15.00
4.00 20.00 240.00 20.00
5.00 25.00 300.00 25.00
6.00 30.00 360.00 30.00
7.00 35.00 420.00 35.00
8.00 40.00 480.00 40.00
9.00 45.00 540.00 45.00
10.00 50.00 600.00 50.00
11.00 55.00 660.00 55.00
12.00 60.00 720.00 60.00
13.00 65.00 780.00 65.00
14.00 70.00 840.00 70.00
15.00 75.00 900.00 75.00
16.00 80.00 960.00 80.00
17.00 85.00 1020.00 85.00
18.00 90.00 1080.00 90.00
19.00 95.00 1140.00 95.00
20.00 100.00 1200.00 100.00
3.14.3 Validation Results
See Fig. 3-20.
If the information that is shown (or printed) matches the
initial readings within system specications, then it can
be veried that the calibration and conguration is as
originally set. It can also be veried that the transmitter’s
response falls within acceptable tolerances. The system has
passed validation tests. Using the Save/Print feature built
into the transmitter allows the ability to comply with the
record-keeping needed for many processes by regulatory
agencies.