NFPA Standard-Specific Requirements
40 Autopulse-442R 50098:F 05/24/2001
%1)3$5HPRWH6WDWLRQ)LUH$ODUP6\VWHP
Intended for connection to a polarity reversal circuit of a remote station receiving unit having
compatible ratings. All connections are power-limited and supervised with the exception of the
reverse polarity loop. Supervision of the loop is the responsibility of the receiver.
1
1
1
1
1
1
1
1
1
1
5
1
1
1
3
7
2
2
2
2
2
2
2
2
2
2
2
2
2
4
8
6
1
12
14
10
13
9
11
--
--
K
--
--
--
K
K | | | | | | | | | | K
+
-
-
+
H
4XTM
Transmitter Module
(activated polarities shown)
Remote Alarm
Remote Trouble
1
2
3
4
+
+
-
-
Fire•Lite RS82-9
Remote Station
Receiver
UL listed
5(035266FGU
Power Transformer
Recommended Types:
ELPower EP 1250C
Power Sonic PS 1245
Power Sonic PS 1260
Power Sonic PS 1265
YUASA NPG-12 or equivalent
Maximum Battery Size
6.0 X 2.6 X 4.1 in.
(15.24 x 6.6 x10.41 cm)
Alarm Signal Input 3
}
Alarm Signal Input 4
}
Alarm Signal Input 5
}
Alarm Signal Input 6
}
Alarm Signal Input 7
}
Alarm Signal Input 8
}
Alarm Signal Input 9
}
Remote Station
Master Board
(RSM-9)
Control Card
(RSC) Circuit Side
Filter
Cap
Signalling Relay
for Bells and
Dry Contacts
N.C.2
N.O.2
POLE 2
N.C.1
N.O.1
POLE 1
A.C. Circuit Breaker
120 VAC
1.2 AMPS
Press to Reset
Battery
Circuit
Fuse
8 AG
5 A
Grounding Terminal
}
120 VAC 1.2 A
50-60 Hz Input
N/C
BATT
CONN
Bell
or
Horn
10K
ELR
Zone Card (RSZ)
Circuit Side
Optional Zone
Card (RSZ)
Circuit Side
Dry Supplementary Contacts,
Rated
3A, 120 VAC Resistive
3A, 30 VDC Resistive