28 AUTOPULSE IQ-396X Programming Doc. 50402:B 07/22/96
Programming, continued
Cross Zoning lets you program the control panel to activate a releasing zone
and any output mapped to the releasing zone. (If not using Cross Zoning, set
CROSS= to N.) The following table summarizes the types of cross zoning and
the conditions for activating a releasing zone.
epyT...lenaplortnocehtnehwsetavitcA
Ynetehtfoenootdeppamerataht,srotcetederomroowtspirT
.)9R-0R(senozgnisaeler
ZerawtfostnereffidowtotdeppamsrotcetederomroowtspirT
.)9R-0R(senozgnisaelernetehtfoenootdeppamdnasenoz
HnetehtfoenootdeppamrotcetedekomsenotsaeltaspirT
otdeppamrotcetedtaehenotsaeltadna)9R-0R(senozgnisaeler
.)9R-0R(senozgnisaelernetehtfoeno
Cross Zoning
Only the first non-special
zone listed in the zone map
is used to determine
Cross=Z.
The following explanations apply to the examples listed in the table:
Cross=N  An alarm from any detector activates the releasing circuit.
Cross=Y  An alarm from any two detectors in the system activates the
releasing circuit.
Cross=Z  Release requires the activation of two detectors mapped to
different zones: D101 and D102 cannot activate the releasing circuit because
both detectors are mapped to Z01; D101 and D103 can activate the releasing
circuit because they are mapped to different zones.
Cross=H  Release requires activation of heat detector D104 and one smoke
detector (D101, D102, or D103).
Example: Devices Mapped to Releasing Zones
Cross Zoning Types
Cross Zoning Examples
The following table contains examples of devices mapped to releasing zones
(ZR1 stands for Releasing Zone 1).
Soak Timer (NFPA 16
applications only)
The Soak Timer specifies the length of time (0000 to 9999 seconds) to dump
releasing agents when a zone activates. When the Soak Timer elapses, the
control panel automatically shuts off the releasing solenoids for the active zone.
To program a Soak Timer for a point, follow these instructions:
1) Select a Releasing Zone (R0-R9) from the Special Functions screen to display
the Release Function screen.
2) Move the cursor to Soak and enter the value for the Soak Timer: 0000=no
Soak Timer; or 0001-9999 seconds to select the amount of time for the Soak
Timer.
eciveD
sserddA
epyTeciveDgnippaMenoZ
101DekomSrotceteD10Z1RZ
201DekomSrotceteD10Z1RZ
301DekomSrotceteD20Z1RZ
401DtaeHrotceteD20Z1RZ
10B)tkCleR(tiucriCtuptuO1RZ
PRG RELEASE FUNCTION RELEASE CONTROL
DELAY=00 ABORT=ULI CROSS=N SOAK=0600 R00
Soak Timer Value = 600 seconds

Other manuals for Ansul AUTOPULSE IQ-396X

Related product manuals