SECTION VII
UL EX-4510 7-15-02 Page 7-3
REV. 1
Testing And Placing In Service
DISCHARGE TEST (Continued)
8. Remove all empty INERGEN agent cylinders and
install full ones. Attach all actuators.
9. Remove all empty INERGEN agent cylinders from the
area. Deliver the empty cylinders to an authorized
INERGEN Agent Fill Location.
10. Record discharge test information with the authority
having jurisdiction and inform all concerned personnel
that the system is now back in normal working order.