SECTION VIII
UL EX-4510 12-1-01 Page 8-4
Resetting And Recharge
3300 psi
(277.5 Bar)
3200 psi
(220.6 Bar)
3100 psi
(213.8 Bar)
3000 psi
(206.9 Bar)
2900 psi
(200.0 Bar)
2800 psi
(193.1 Bar)
2700 psi
(186.2 Bar)
2600 psi
(179.3 Bar)
2500 psi
(172.4 Bar)
2400 psi
(165.5 Bar)
2300 psi
(158.6 Bar)
0 °F 20 °F 40 °F 60 °F 80 °F 100 °F 120 °F 140 °F
(–18 °C) (–7 °C) (4 °C) (16 °C) (27 °C) (38 °C) (49 °C) (60 °C)
MAXIMUM OVERFILL 3000 PSI (207 BAR) @ 70 °F (21 °C)
NOMINAL 2900 PSI (200 BAR) @ 70 °F (21 °C)
5% PRESSURE LOSS