The Booster Actuator, Part No. 428949, is used when elec-
tric actuation is required on the 1 in. selector valve, 2 in.
selector valve, or the CV-98 cylinder valve. The actuator
mounts directly to the component and then a HF electric
actuator mounts to the top of the booster actuator.
The Booster Actuator requires resetting after actuation. A
Reset Tool, Part No. 429847, is available for this use.
System Components
UL EX-4510 12-1-01 Page 1-6
Booster Actuator
ANSUL INCORPORATED, ONE STANTON STREET, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2001254 ©2001 Ansul Incorporated Litho in U.S.A.
ANSUL and INERGEN are trademarks of Ansul Incorporated or its affiliates.
006037
Ø 2.50
3.025
1 1/4 – 18 UNEF
1 1/8 – 18 UNEF
Component Material Approvals
Booster Stainless Steel UL Listed
Actuator and Brass (EX-4510)
ANSUL
®
®

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ansul INERGEN and is the answer not in the manual?

Ansul INERGEN Specifications

General IconGeneral
AgentINERGEN
ComponentsNitrogen, Argon, Carbon Dioxide
Agent Composition52% Nitrogen, 40% Argon, 8% Carbon Dioxide
StorageHigh-pressure cylinders
Cylinder MaterialSteel
ApplicationTotal flooding fire suppression
Design Concentration34.2% - 50% (depending on fuel type)
Storage Pressure3000 psi (207 bar)
Environmental ImpactZero ozone depletion potential, no global warming potential
SafetySafe for use in occupied spaces when design concentration is maintained
Extinguishing MechanismOxygen reduction to below combustion level
ApprovalsUL, FM
Cylinder SizesVarious sizes
Discharge TimeTypically less than 60 seconds
Typical ApplicationsData centers, telecommunications, museums, archives