Nozzles – Nozzles are designed to direct the
discharge of INERGEN agent using the
stored pressure from the cylinders. Nozzles
are available in either 360° or 180° discharge
patterns. The system design specifies the
nozzle and orifice size to be used for proper
flow rate and distribution pattern. The nozzle
selection depends on the hazard and loca-
tion to be protected.
Pressure Reducer – The pressure reducer
is required in the distribution piping to restrict
the flow of INERGEN agent, thus reducing
the agent pressure down stream of the
reducer. The pressure reducer contains a
stainless steel orifice plate which is drilled to
the specific size hole required based on the
hydraulic calculation. The orifice plate pro-
vides readily visible orifice identification. The
pressure reducer is available in nine sizes:
1/2 in., 3/4 in., 1 in., 1 1/4 in., 1 1/2 in., 2 in.,
2 1/2 in., 3 in., and 4 in. NPT.
Pipe and Fittings – System manifold piping
must be constructed to withstand a mini-
mum pressure of 3000 psi (206.9 bar).
Distribution piping downstream from the ori-
fice union must be constructed to withstand
the maximum downstream pressure as
determined by the flow calculation.
Limitations – The INERGEN system must
be designed and installed within the guide-
lines of the manufacturer’s design, installa-
tion, operation, inspection, recharge, and
maintenance manual. The ambient temper-
ature limitations are 32 °F to 130 °F (–0 °C
to 54 °C). All AUTOPULSE Control Systems
are designed for indoor applications and for
temperature ranges between 32 °F and
120 °F (0 °C and 49 °C).
TECHNICAL DATA
Applicable Standards: The INERGEN
system complies with NFPA Standard 2001,
Standard for Clean Agent Fire Extinguishing
Systems, and EPA Program SNAP,
Significant New Alternate Policy.
System is listed by Underwriters
Laboratories, Inc. (UL).
Agent is listed and approved by Underwriters
Laboratories, Inc. (UL) and Factory Mutual
Research Corporation (FMRC).
INSTALLATIONS
All system components and accessories
must be installed by personnel trained by the
manufacturer. All installations must be per-
formed according to the guidelines stated in
the manufacturer’s design, installation,
operation, inspection, recharge, and
maintenance manual.
AVAILABILITY AND COST
Availability – INERGEN Systems are sold
and serviced through a network of indepen-
dent distributors located in many countries.
Cost – Cost varies with type of system
specified, size, and design.
PRODUCT WARRANTY
Warranty – The components of the fire
suppression system supplied by Ansul Inc.
(‘‘Ansul’’) are warranted to you as the original
purchaser for one year from the date of
delivery against defects in workmanship and
material. Ansul will replace or repair any
Ansul supplied components, which, in its
opinion, are defective and have not been
tampered with or subjected to misuse,
abuse, or exposed to highly corrosive condi-
tions provided that written notice of the
alleged defect shall have been given to
Ansul within 30 days after discovery thereof
and prior to the expiration of one year after
delivery, and further provided that if Ansul so
instructs, such article or part thereof is
promptly returned to Ansul with shipping
charges prepaid.
Disclaimer of Warranty and Limitation of
Damage – The warranty described above is
the only one given by Ansul concerning this
system. ANSUL MAKES NO OTHER
WARRANTIES OF ANY KIND, WHETHER
EXPRESS OR IMPLIED, INCLUDING THE
WARRANTIES OF MERCHANTABILITY
AND FITNESS FOR PARTICULAR
PURPOSE. ANSUL’S MAXIMUM RESPON-
SIBILITY FOR ANY CLAIMS WHETHER IN
CONTRACT, TORT, NEGLIGENCE,
BREACH OF WARRANTY, OR STRICT
LIABILITY SHALL BE LIMITED TO THE
PURCHASE PRICE OF THE SYSTEM.
UNDER NO CIRCUMSTANCES SHALL
ANSUL BE RESPONSIBLE FOR SPECIAL,
CONSEQUENTIAL, OR INCIDENTAL
DAMAGES OF ANY KIND. Ansul does not
assume or authorize any other person to
assume for it any additional liability in
connection with the sale of this system.
For repairs, parts, and service of the Ansul
fire suppression system, contact a local
Ansul international representative, or Ansul
Incorporated, Marinette, WI 54143-2542,
715-735-7411.
FALSE DISCHARGE WARRANTY
Subject to the conditions set forth below,
Ansul will, as purchaser’s sole remedy,
replace INERGEN gas and pay reasonable
costs to recharge the INERGEN/Detection
and Control System where, in Ansul’s opin-
ion, the discharge has occurred due to a
defect in the material or workmanship of the
products provided by Ansul. This warranty is
extended only to the original purchaser of the
INERGEN/Detection and Control System and
only for a period of one year from the date of
installation of the INERGEN/Detection and
Control System.
Ansul will only replace INERGEN gas and
pay reasonable costs to recharge the
INERGEN/Detection and Control System
where the discharge occurs due to a defect
in the material or workmanship of the
products provided by Ansul. For example,
Ansul will not be responsible for discharges
due to faulty maintenance or installation or
service, intentional acts by the owner or third
parties, or circumstances over which Ansul
has no control. Ansul will not be responsible
for discharges of the INERGEN/Detection
and Control System which occur if the
INERGEN/Detection and Control System,
as initially installed, has been altered or
modified.
This warranty shall be effective only if the
original purchaser maintains a semi-annual
service agreement for the INERGEN/
Detection and Control System with an
Authorized Ansul Distributor from the date of
installation. This warranty covers only those
INERGEN/Detection and Control Systems
purchased from Ansul or its Authorized
Distributors and only those INERGEN/
Detection and Control Systems which incor-
porate and use only hardware and compo-
nents, including detection and control
devices manufactured, sold, or approved by
Ansul. This warranty may not be assigned or
transferred to others.
Ansul Product Services Department must be
notified within three days of the discharge of
the INERGEN/Detection and Control System
and must approve the cost of INERGEN gas
and recharge service in advance.
Except as provided above, ANSUL MAKES
NO WARRANTIES OF ANY KIND,
WHETHER EXPRESSED OR IMPLIED,
INCLUDING THE WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE, UNDER NO
CIRCUMSTANCE SHALL ANSUL HAVE
ANY LIABILITY FOR CONSEQUENTIAL,
INCIDENTAL, SPECIAL OR SIMILAR
DAMAGES. ANSUL SHALL HAVE NO
LIABILITY FOR ANY DAMAGES DUE TO
DELAY IN RECHARGING THE
‘‘INERGEN’’/DETECTION AND CONTROL
SYSTEM. ANSUL’S MAXIMUM LIABILITY
FOR DIRECT DAMAGES IS LIMITED TO
THE REPLACEMENT OF INERGEN GAS
AND REASONABLE COSTS TO
RECHARGE THE ‘‘INERGEN’’/DETECTION
AND CONTROL SYSTEM.
This warranty is not effective unless Ansul
Form No. F-9346 is completed and returned
to Ansul within 10 days of the commissioning
of the INERGEN/Detection and Control
System.
MAINTENANCE
Maintenance is a vital step in the perfor-
mance of a fire suppression system. As
such, it must be performed by an authorized
Ansul distributor in accordance with NFPA
2001 and the manufacturer’s design, installa-
tion, recharge, and maintenance manual.
When replacing components on the Ansul
system, use only Ansul approved parts.
TECHNICAL SERVICES
For information on the proper design and
installation, contact a local international
authorized INERGEN System distributor.
The Ansul applications engineering depart-
ment is also available to answer design and
installation questions. Call 715-735-7411.