SECTION VI
UL EX-4510 12-1-01 Page 6-1
All installations are to be performed in accordance with the
parameters of this manual and all appropriate codes and
standards from the local, state, and federal authority having
jurisdiction.
Before the INERGEN system is installed, the qualified
installer should develop installation drawings in order to
locate the equipment, to determine an actuation and distrib-
ution piping routing, and to develop a bill of material.
For successful system performance, the INERGEN system
components must be located within their approved temper-
ature ranges. The ambient temperature range is 32 °F to
130 °F (0 °C to 54 °C). All AUTOPULSE Control Systems
are designed for indoor applications and for temperature
ranges between 32 °F to 120 °F (0 °C to 49 °C).
MOUNTING COMPONENTS
Cylinder/Bracket Assembly
INERGEN cylinders may be located inside or outside the
protected space, although it is preferable to locate them
outside of the space. They must not be located where they
will be exposed to a fire or explosion in the hazard. When
they are installed within the space they protect, a remote
manual control must be installed to release the system
safely from outside the hazard area.
The cylinders should be installed so that they can be easily
removed after use for recharging. Cylinders must be
installed indoors. Do not install the cylinders where they are
exposed to direct sun rays. Cylinders may be installed hori-
zontal if properly bracketed.
See Figures 1 through 4 for detailed mounting height infor-
mation for all cylinder bracketing.
FIGURE 1
001868
Installation
ANSUL
®
®
Bracketing Without Uprights – Single Cylinder
Clamp Installation – INERGEN Cylinder Assembly
Cylinder Size Dimension A Dimension B Dimension C Dimension D
cu.
ft. (cu. m) in. (cm) in. (cm) in. (cm) in. (cm)
570 (16.1) 14 (36) 38 (97) 12 (31) 15 1/8 (38)
B
A
C
MOUNTING HOLES – 2
HAVING 11/16 IN. DIAMETER
2 IN. X 1 IN. X 3/16 IN.
STEEL CHANNELS
1/2 IN. X 1 1/4 IN. BOLTS AND
NUTS (BOLT HEADS WELDED
TO CHANNELS)
2 IN. X 3/16 IN.
STEEL STRAPS
D