INSTALLING ACTUATORS (Continued)
Electric Actuator
A maximum of two HF electric actuators can be installed on
a single AUTOPULSE release circuit.
Installing the Booster Actuator
1. Make certain the booster actuator is in the set (armed)
position. This can be confirmed by visually checking
the position of the top and bottom pins. When in the
set position, the top pin will be approximately flush
with the top of the actuator. The bottom pin will be
flush with the inside surface of the actuator. If the actu-
ator requires setting, use the arming tooling, Part No.
429847, and follow the instructions listed in "Resetting
the Booster Actuator.ā€
2. Hand tighten the actuator unto the cylinder valve or
the selector valve.
Installing the HF Actuator
1. Make certain the HF actuator is set (armed) position.
When in the set position, the top pin will be flush with
the top of the actuator. If the actuator requires setting,
use the arming too, Part No. 75433, and follow the
instructions listed in "Resetting the HF Actuator".
2. Hand tighten the HF actuator onto the booster actua-
tor.
3. If all other installations are complete, connect electri-
cal power to the HF actuator. Refer to appropriate
AUTOPULSE manual for detailed wiring information.
INSTALLING ACCESSORIES
Manual Pull Station
Depending on the type of actuation being used, there are
different pull stations available. Remote pull stations can be
either mechanical or electric.
MECHANICAL PULL STATION TO ANSUL AUTOMAN
II-C RELEASE – To install a mechanical pull station com-
plete the following steps:
1. Insert ring pin in ANSUL AUTOMAN II-C release. See
Figure 13.
FIGURE 13
001894
2. If necessary, remove cartridge and install safety ship-
ping cap on cartridge.
3. Select a convenient location in the path of exit for
mounting the pull station(s) to the wall. Height and
location of pull station should be determined in accor-
dance with authority having jurisdiction.
The total length of the wire rope used for each manual
pull station within a system must not exceed 125 ft.
(38 m).
The maximum number of pulley elbows that may be
used per system is 18 of Part Nos. 423250 and
415670.
4. If junction box(es) is used, fasten a 4 in. (10 cm) junc-
tion box to wall or in wall where pull station is to be
mounted, with mounting screws positioned so that
when pull station cover is positioned in place, the
printing will appear right side up and readable.
SECTION VI
UL EX-4510 12-1-01 Page 6-14
Installation
CAUTION
!
Make certain all electric power from the panel to the
actuator has been disconnected. Failure to disconnect
power may cause system to accidentally discharge.
CAUTION
!
Make certain all electric power from the panel to the
actuator has been disconnected. Failure to disconnect
power may cause system to accidentally discharge.