Specifications
2-2
2.2 Performance specifications
DC power supply superimposed total frame, cyclic method
Frame/bit synchronization
512 points (256 inputs, 256 outputs)
Number of connectable units
Transmission distance /
Supply current
DP-DN allowable
supply current
Over 100 m, 200 m or less
Over 100 m, 200 m or less
Over 100 m, 200 m or less
Transmission cable disconnection detecting function, Transmission
cable short-circuit detecting function, Transmission circuit drive power
supply voltage drop detecting function, ID (address) duplication/no
setting detecting function
General-purpose, 2-core/4-core cable (VCTF, VCT 0.75 to 1.25
mm2, Rated temperature: 70C)
General-purpose cable (0.75 to 1.25 mm2, Rated temperature:
70C)
Dedicated flat cable (0.75 mm2 / 1.25 mm2, Rated temperature:
90C)
T-branching, multi-drop, star-branching, Tree-branching
Voltage: 21.6 to 27.6 V DC (24 V DC -10 to +15%) Ripple: 0.5 V p-p
or less
Recommended voltage: 26.4 V DC (24 V DC +10%)
To comply with the UL standard, be sure to use a 24 V DC stabilized
power supply for NEC Class 2 output.
Bit transmission cycle time
150 mA (not including the load)
PROFINET
performance level
NT, RT (Incompatible with IRT)