8 InRow™ Chilled Water Air Conditioners Technical Specifications 990-4618A-001
Optional features
Cable water detector A leak detection cable is placed on the floor or sub-floor around all
possible leak sources. If water or other conductive liquids contact
the cable anywhere along its length, the microprocessor controller
visually and audibly announces a leak. The 6.1-m (20-ft) cable may
be cascaded to make custom lengths up to 24.4 m (80 ft).
Network cable Various lengths of network cable are available to ship with your
cooling system. The network cable is used to interconnect multiple
cooling units in a redundant group, as well as to connect the
network management card to your Local Area Network (LAN).
Power trough Overhead power distribution between adjacent NetShelter racks
allows for removal of the InRow CW unit without disrupting
overhead power cabling.
Data partition Overhead cable distribution between adjacent NetShelter racks
allows for removal of the InRow CW unit without disrupting
overhead cabling.
Height adapters To match the height of the InRow CW unit to various rack heights,
height adapters are available for NetShelter 42-U VX, 45-U SX,
and 48-U SX racks.
Disposable pleated filter
(ACRC100 series only)
The filtration of conditioned air is extremely vital to maintaining
the clean, particle-free environment required by electrical
equipment. As an optional feature, the system uses a 50.8-mm (2-
in) pleated, deep- loading, 30% ASHRAE 52.1 filter (MERV 8 per
ASHRAE 52.2).
85% ASHRAE 52.1 filter
(ACRC500/ACRP500 series only)
Electrical equipment requires clean, particle free air, thus making
the filtration of the air extremely important. Optionally, the system
uses an 85% efficient, 102-mm (4-in), deep loading, pleated filter.
Deeper filters produce a lower pressure drop, requiring less energy
during normal operation. The 100% synthetic media will not
absorb moisture and is resistant to most common chemicals. The
filter is moisture resistant up to a 100% relative humidity. Filters
are easily replaceable from the rear of the unit. (MERV 13 per
ASHRAE 52.2, EN779 F7).
Rack Air Containment The Containment Solution isolates the airflow of individual racks
and InRow cooling units from the whole IT environment,
increasing efficiency while allowing for high density deployment.
Aisle Containment The Containment Solution isolates pods (two rows of racks sharing
a common aisle) from the whole IT environment, increasing
cooling efficiency at any density. For details, see “Hot Aisle
Containment System” on page 4.