10 InRow™ Chilled Water Air Conditioners Technical Specifications 990-4618A-001
Functions
• Supply and Return Air Conditions
• Operational Mode Control
• Event Logging
• Alarms
• Redundant Group Control
• Fan Speed Adjustment
• Input/Output Module Programming
Logging
The event log keeps a record of all alarms and events. Each event log contains a time/date stamp as well as
operating conditions at the time of occurrence. The controller also displays run time, in hours, for major
components (air filters, fans, power supplies, and condensate pump).
Control
The backlit, four-line by twenty-character display interface is protected by a configurable password.
• Supply Temperature Setpoint 15–30.2°
C (59–86.4°F)
• Rack Inlet Temperature Setpoint 18–32°C (64.4–90°F)
• Rack Inlet High Temperature Alarm 0–100°C (32–212°F)
• CW Inlet High Temperature Alarm 0–37.7°C (32–100°F)
• Air Supply Temperature High Alarm 0–100°C (32–212°F)
• Return Temperature High Alarm 0–100°C (32–212°F)