990-4618A-001 InRow™ Chilled Water Air Conditioners Technical Specifications 27
Note: All values are accurate to ± 0.73 kW (2500 BTU/hr) and based on full speed with standard filters.
Note: Any CW flow rate of 3.9 GPM-5.0 GPM may have increased error in Flow Rate and Power Calculation. A Fluid Flow
Fault may result. Any flow rate under 3.0 GPM may also display as 0 in Flow Rate and Power Calculation.
Note: For ACRC500/ACRP500 series, reduce airflow and cooling capacity specifications by 7% for cooling units run at low
input voltage (380V).
40.6°C DB, 21.6°C WB (105°F DB, 70.8°F WB)
6.6°C (12°F) ACRC100 30.7 (105000) 30.7 (105000) 1.00 1.14 (18.1) 91.62 (30.7)
7.7°C (14°F) ACRC100 29.6 (10100) 29.6 (10100) 1.00 0.95 (15.0) 64.27 (21.5)
8.8°C (16°F)
ACRC100 28.7 (98000) 28.7 (98000) 1.00 0.8 (12.6) 46.92 (15.7)
ACRC500/ACRP500 69.6 (238000) 69.6 (238000) 1.00 1.9 (29.9) 86 (28.9)
10°C (18°F)
ACRC100 27.5 (94000) 27.5 (94000) 1.00 0.69 (10.8) 35.3 (11.8)
ACRC500/ACRP500 66.1 (226000) 66.1 (226000) 1.00 1.6 (25.3) 63 (21.02)
11.1°C (20°F)
ACRC100 26.4 (90000) 26.4 (90000) 1.00 0.59 (9.4) 27.18 (9.1)
ACRC500/ACRP500 62.7 (214000) 62.7 (214000) 1.00 1.4 (21.7) 46 (15.5)
Temperature
DB, WB
°C (°F)
CW
Delta T
°C (°F)
Model Series
Total Net Capacity
Sensible Net
Capacity
Sensible
Heat Ratio
CW
Flow Rate
Total CW Pressure
Drop
kW (BTU/hr) kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O)