990-4618A-001 InRow™ Chilled Water Air Conditioners Technical Specifications 53
Guide Specifications
Guide Specification for InRow CW Units
THIS GUIDE SPECIFICATION IS WRITTEN IN ACCORDANCE WITH THE CONSTRUCTION SPECIFICATIONS
INSTITUTE (CSI) MASTERFORMAT. THIS SECTION MUST BE CAREFULLY REVIEWED AND EDITED BY THE
ARCHITECT OR THE ENGINEER TO MEET THE REQUIREMENTS OF THE PROJECT.
COORDINATE THIS SECTION WITH OTHER SPECIFICATION SECTIONS IN THE PROJECT MANUAL AND WITH
THE DRAWINGS. WHERE REFERENCE IS MADE THROUGHOUT THIS SECTION TO “PROVIDE”, “INSTALL”,
“SUBMIT”, ETC., IT SHALL MEAN THAT THE CONTRACTOR, SUBCONTRACTOR, OR CONTRACTOR OF LOWER
TIER SHALL “PROVIDE”, “INSTALL”, SUBMIT”, ETC., UNLESS OTHERWISE INDICATED.
THIS SECTION IS WRITTEN TO INCLUDE THE 2004 MASTERFORMAT AND THE 1995 MASTERFORMAT
VERSIONS. WHERE APPLICABLE, THESE ITEMS ARE BRACKETED AND, IN EACH CASE, UNLESS OTHERWISE
INDICATED, THE FIRST CHOICE APPLIES TO THE 2004 MASTERFORMAT AND THE SECOND CHOICE APPLIES
TO THE 1995 MASTERFORMAT.
PART 1 — GENERAL
1.1 SUMMARY
A. The environmental control system shall be designed specifically for precision temperature or humidity
control applications. It will automatically monitor and control cooling, filtering, heating, humidifying,
and dehumidifying functions for the conditioned space. The system shall be built to the highest quality
engineering and manufacturing standards, and shall be floor mounted and configured for horizontal
airflow, with draw-through air pattern, to provide uniform air distribution over the entire face of the
coil.
1.2 DESIGN REQUIREMENTS
A. The system shall be as described in the following specification as manufactured by APC.
1. Model: ____________________________.
2. Total net cooling capacity: _______________ MBH (kW).
3. Sensible net cooling capacity: ____________ MBH (kW).
4. Return air dry bulb temperature: _______________ º F (º C) DB.
5. Return air wet bulb temperature: _______________ º F (º C) WB.
6. Humidity: __________________________% RH.
7. Air Volume: _______________________ CFM (L/s).
8. Humidifier capacity: _________________ lbs/hr (kg/hr) (ACRP500 series only).
9. Electrical supply: ________ V, _________ Hz.
1.3 SUBMITTALS
A. Submittals shall be provided with the proposal and shall include: capacity data, electrical data,
physical data, electrical connection drawing, and piping connection drawing.