58 InRow™ Chilled Water Air Conditioners Technical Specifications 990-4618A-001
L. CONDENSATE PUMP
1. ACRC100 Series
a. The factory-installed condensate pump is piped internally to the condensate pan. It is capable
of pumping 5 L/h (1.3 GPH) liquid a maximum distance of 15.2 m (50 ft), which may include
a maximum lift of 4.9 m (16 ft). Dual floats are included with the unit. One float is used for
condensate pump control, the other to generate condensate pan overflow alarms.
2. ACRC500/ACRP500 Series
a. The factory-installed condensate pump is piped internally to the condensate pan. It is capable
of pumping 31.8 l/h (8.45 GPH) liquid a maximum distance of 18 m (60 ft), which may include
a maximum lift of 3.5 m (11.5 ft). Dual floats are included with the unit. One float is used for
condensate pump control, the other to generate condensate pan overflow alarms.
M. FILTERS
1. ACRC100 Series
a. The standard air filter shall be <20% efficient per ASHRAE 52.1, MERV 1 per ASHRAE 52.2,
1/2-in washable mesh filter.
b. The optional air filter shall be high capacity 2-in pleated, UL 900 Class 2, Moisture with
average atmospheric dust spot efficiency of 30% per AHRAE Standard 52.1, MERV 8 per
ASHRAE 52.2.
2. ACRC500/ACRP500 Series
a. The standard filters shall be 30% efficient per ASHRAE Standard 52.1, UL Class 2 (MERV 8
per ASHRAE 52.2). Filters shall be EN779 G4 efficient.The 96 mm (3.75 in) deep, pleated
filters shall be replaceable from the rear of the unit.
b. The optional filter shall be 85% efficient per ASHRAE Standard 52.1 (MERV 13 per
ASHRAE 52.2, EN779 F7).
N. HUMIDIFIER (ACRP500 series only)
1. Humidifier shall be able to modulate capacity. The humidifier shall be self-contained, steam-
generating type, factory piped and wired, with disposable cylinder and automatic solid-state
control circuit. Humidifier canisters shall be replaceable. The humidifier controller shall
communicate directly to the microprocessor controller and provide complete status and control at
the operator interface. Humidifier shall control flush cycling and conductivity via automated
controls. Humidifier shall be capable of producing up to 6.6 lb (3 kg) of steam per hour.
O. ELECTRIC REHEAT (ACRP500 series only)
1. Reheat elements shall be low watt density, wired for three-phase, loaded equally on all three phases
and shall be electrically and thermally protected by both automatic and manual reset cutouts.
Reheat capacity shall be 9 kW.
2. Reheat coils shall be stainless steel, fin tubular construction. Heater casing shall be 20 gauge G90
galvanized steel.
3. Heater shall be provided with self-engaging electrical connectors upon installation. Heater with
manually connected conductors are not acceptable.