Metered Rack PDU User’s Guide16
• A Stat field reports the Rack PDU status.
Stat : P+ N+ A+
If P+ is not displayed, contact APC support staff. See “APC Worldwide Customer
Support” on page 111.
P+ The APC operating system (AOS) is functioning properly.
IPv4
only
IPv6
only
IPv4 and
IPv6*
Description
N+ N+ N4+ N6+ The network is functioning properly.
N? N6 N4? N6? A BOOTP request cycle is in progress.
N– N6 N4- N6- The Rack PDU failed to connect to the network.
N! N6! N4! N6! Another device is using the Rack PDU IP address.
* The N4 and N6 values can be different from one another: you could, for example, have
N4- N6+.
A+ The application is functioning properly.
A– The application has a bad checksum.
A? The application is initializing.
A! The application is not compatible with the AOS.