Metered Rack PDU User’s Guide34
Device Command Descriptions
bkLowLoad
Access: Administrator, Device User
Description: Set or view the bank low-load threshold current in Amps. You can specify all banks, a
single bank, a range, or a comma-separated list of single banks and/or ranges.
Example 1: To set the low-load threshold for all banks to 1A, type:
apc> bkLowLoad all 1
E000: Success
Example 2: To view the low-load threshold setting for banks 1 through 3, type:
apc> bkLowLoad 1-3
E000: Success
1: 1 A
2: 1 A
3: 1 A
bkNearOver
Access: Administrator, Device User
Description: Set or view the bank near-overload threshold current in Amps. You can specify all banks,
a single bank, a range, or a comma-separated list of single banks and/or ranges.
Example 1: To set the near-overload threshold for all banks to 10A, type:
apc> bkNearOver all 10
E000: Success
Example 2: To view the near-overload threshold setting for banks 1 through 3, type:
apc> bkNearOver 1-3
E000: Success
1: 10 A
2: 10 A
3: 10 A
bkOverLoad
Access: Administrator, Device User
Description: Set or view the bank overload threshold current in Amps. You can specify all banks, a
single bank, a range, or a comma-separated list of single banks and/or ranges.
Example 1: To set the bank overload threshold for all banks to 13A, type:
apc> bkOverLoad all 13
E000: Success
Example 2: To view the bank overload threshold setting for banks 1 through 3, type:
apc> bkOverLoad 1-3
E000: Success
1: 13 A
2: 13 A
3: 13 A