Metered Rack PDU User’s Guide40
sensorName
Access: Administrator, Device User
Description: Set or view the name assigned to the Rack PDU Temp/Humidity port.
Example 1: To set the name for the port to “Sensor1,” type:
apc> sensorName Sensor1
E000: Success
Example 2: To then view the name for the sensor port, type:
apc> sensorName
E000: Success
Sensor1
tempHigh
Access: Administrator, Device User
Description: Set or view the high-temperature threshold in either Fahrenheit or Celsius.
Example 1: To set the high-temperature threshold to 70º Fahrenheit, type:
apc> tempHigh F 70
E000: Success
Example 2: To view the high-temperature threshold in Celsius, type:
apc> tempHigh C
E000: Success
21 C
Example 3: To view the high-temperature threshold in Fahrenheit, type:
apc> tempHigh F
E000: Success
70 F
tempMax
Access: Administrator, Device User
Description: Set or view the max-temperature threshold in either Fahrenheit or Celsius.
Example 1: To set the max-temperature threshold to 80º Fahrenheit, type:
apc> tempMax F 80
E000: Success
Example 2: To view the max-temperature threshold in Celsius, type:
apc> tempMax C
E000: Success
27 C
Example 3: To view the max-temperature threshold in Fahrenheit, type:
apc> tempMax F
E000: Success
80 F