Technical Support Line +44 (0)23 9244 2706 Doc 39215-410 Iss 2
Isolator Specicaon
VSO, Isolate Voltage 13-16V
VSC, Reconnect Voltage 12-14V
IC, Connuous Current—
Switch Closed
1A max
IS, Switching Current 3A max
IL, Leakage Current 300µA max
Condions for Holding
The door will hold if all the following
condions are met:
• There is loop communicaon
• The device is suciently charged (45
minutes)
• No faults on the device
• The device has a valid address (not 0 or
127)
• There is no Alarm condion indicated by
the panel
Maintenance
Fire door holders should be tested weekly as
part of the re-system test procedures. For
opmum holding force, the face of the magnet
and keeper plate should be kept clean and free
from damage. To comply with BS EN 1155, this
device should not be used to hold open a door at
less than 65°. There are no user-serviceable
parts in this door retainer.
EMC Direcve
The Addressable Door Retainer complies with
the essenal requirements of the EMC Direcve
2014/30/EU, provided that it is used as
described in this installaon guide.
Construcon Products Regulaon (EU)
305/2011
The Addressable Door Retainer complies with
the essenal requirements of the Construcon
Products Regulaon (EU) 305/2011
Technical Support Line +44 (0)23 9244 2706 Doc 39215-410 Iss 2
Addressable Door Retainer (ADR)
Product overview
Product: Addressable Door Retainer (ADR)
Part No: 55000-982APO
Digital Communicaon: XP95 compable
Product informaon
Door retainers ensure buildings are accessible for all by holding re doors in the open posion then
releasing and closing them according to the re system design. The Apollo Addressable Door Retainer
is an XP95 device designed for installaon directly onto an addressable loop and is suitable for use on
all types of re door, including crical actuaon doors.
• Integrated loop isolator
• Extra low voltage usage
• Suitable for crical actuaon (Category A) installaons*
• Failsafe by design
• Patented permanent magnet technology
• Doors and zones can be individually controlled
• 200N holding force rang
• Surface or semi-ush wall mounted
• Floor mounng opons via standard bracket
*When connected to a compliant panel