FIGURE 19: WIRING ACCESS COVER LOCATION
90-1884
WIRING
No additional wiring is needed unless:
• the dehumidier is ducted to the HVAC system
• a separate, external control such as a thermostat or
dehumidistat is to be used
• a oat switch, either integral to a condensate pump or
mounted to the condensate pan, is used
Use 18-22 AWG wire for any needed wiring. Access the
dehumidier wiring terminals by pulling off the wiring access
cover near the dehumidier control display (see FIGURE 19).
Snap the wiring access cover back into place after completing
all wiring.
WIRING TO THE HVAC SYSTEM
When the dehumidier is ducted to the HVAC system, it is
recommended that it also be wired to the HVAC system as
shown in FIGURE 20. If ducted to the HVAC system in a
return-to-return conguration, the dehumidier must be wired
to the HVAC system to prevent short-circuiting dehumidied
air directly back to the dehumidier inlet. In a return-to-
supply ducting conguration, running the HVAC fan with the
dehumidier ensures the warm dry air is mixed with room air
before being discharged to the home.
OPTIONAL W & Y WIRING
• Wire the W and/or Y terminal to the HVAC system when using
the ventilation feature of the dehumidier. See VENTILATION
on page 14.
• Wire the dehumidier Y terminal to the HVAC system to
disable the dehumidier compressor from operating when
the air conditioning is running. See ENABLING DEH W/AC on
page 17 for additional setup steps required to access this
feature.
+ - A B ODT VENT DEH
Sensor DampersRemote
FLOAT
Switch
DH DH
Gh Rf Cf Gs YW
HVAC EQUIP.
G
R
C
W
Y
R
C
G
W
Y
OPTIONAL
WIRES
EXISTING WIRE
NEW WIRE
THERMOSTAT
OR ZONE
CONTROL BOARD
HVAC
EQUIPMENT
FIGURE 20: WIRING TO HVAC SYSTEM
90-1859
12