INSTALLER TEST MODE
If everything is properly wired, the dehumidier and all of the
wired components will turn on and off during Installer Test
Mode to demonstrate that all are properly operating. Installer
Test Mode lasts for four (4) minutes. If the ON/OFF button is
pressed during test mode, the dehumidier will exit Installer
Test Mode and return to the OFF screen.
DEHUMIDIFICATION ONLY
If the dehumidier is not already OFF, press the ON/OFF button
to turn it off.
Press and hold the ON/OFF and MODE buttons for 3 seconds.
The measured humidity, AIR SAMPLING and TEST will show on
the display. If wired to the HVAC system, the HVAC blower will
turn on and if there is/are damper(s) wired to the DEH DAMPER
terminals of the control, the damper(s) will energize.
After three (3) minutes the dehumidier compressor will turn on
and DEHUMIDIFYING will replace AIR SAMPLING on the control
screen.
After one minute of compressor operation, all outputs will turn
off and DONE will blink for 3 seconds and then return to the OFF
screen.
ZONING AND/OR VENTILATION
If the dehumidier has been set up for ventilation, VENTILATING
will appear on the display throughout Installer Test Mode, and
the ventilation damper will be energized.
If the dehumidier has been set up for zoning, PRIMARY ZONE
will show on the display for the rst minute of dehumidier
blower operation. After one minute, SECONDARY ZONE will show
on the display and the zone dampers will de-energize.
18