WARNING
Hazardous voltage
can cause electrical shock and burns
Disconnect power before proceeding
with any work on this equipment
Cam Switch
LW39-25
EN60947-5-1 GB 14048.5
Instructions
Before installing the device, please read the instructions.
Summary
Main application
LW39-25 switch is also used to control the start, brake,
clockwise and anti-clockwise of small capacity motor
and the speed governing of two-speed motor.
General product information:
Model specification
LW 39 - 25 - - ··· / - - - -
Installation caution
1) We need to check whether the type meet selection requirement.
2) We must turn off power before installation and recondition.
3) Wiring refer to drawing and turn on the power after you check
carefully.
4) Choose the correct
operational voltage and current
.
5) To prevent impurities metal powder into the product inside.
6) Tighten all terminal screws even if not used.
7) Don't open the parts with red mark.
Technical feature
Parameters
1) Rated insulation voltage(Ui) : 690 V
2) Conventional thermal current(Ith) : 16 A
3)
Power frequency withstand voltage
: 1890 V / 5 s
4) Mechanical life : 30 X 10
4
times
5) Electrical life : AC / 20 X 10
4
times
DC / 10 X 10
4
times
6) Type of fuse used in test of rated conditional short-circuit
currentNT00-25A
7) The ability of terminals wire:
(1) The largest cross-section: 4 mm²; the maximum number
of conductors connected to the terminal: 2
(2) The largest cross-section: 1 mm²; the maximum number
of conductors connected to the terminal: 2
(3) Tightening torque: 1.2 N·m.
8) Usage category
32017.1
Drawing No. : APT0.463.022.10
Operation condition
1) Environment temperature : -25°C to +55°C
2) Relative air humidity 90%
3) Altitude 2000 meters
4) Installation category :
5) Pollution class : 3
The light box schematic diagram
1)
Three terminals [The common is anode] -----default
2)
Three terminals [The common is cathode]
3)
Four terminals [There is no common, Intermediate is cathode]
4)
Four terminals [There is no common, Intermediate is anode]
Note:Be careful to disassemble or assemble
light box , to avoid damaging them.
R R R R
R R R R
X1 X0 X0 X2
X1 X0 X2
R R R R
X1 X0 X2
(+)(-) (-)
(-)(+) (+)
R R R R
X1 X0 X0 X2
(-) (-)(+) (+)
(+) (+)(-) (-)
Siemens Electrical Apparatus Ltd., Suzhou, Tiantai Branch
Jigong Avenue 699- 10 Tiantai, Zhejiang,China
Sales Dept :Tsidi Building No.55,Lane 777,West Guangzhong Road Shanghai
Tel021-56553757 http://www.china-apt.com
DC-13
AC-15
Ie(A)
Ie(A)
Ue(V)
-
24 V
-
-
-
2.5 A
-
48 V 110 V
1.25 A
12 A
220 V
-
8 A
380 V
AC-21
Ie(A)
- - - -
AC-3
Ie(A)
- - - - 12 A
AC-4
Ie(A)
- - - - 10 A
AC-22
Ie(A)
- - - - 25 A
25 A
Usage
category
Switch type
Design number
Specification
Function code
Operating characteristics of code
Relative of nodes or section code
Stages
Panel code
Illuminated code
Handle style
Auxiliary code
Question and Answer IconNeed help?

Do you have a question about the APT LW39-25 Series and is the answer not in the manual?

APT LW39-25 Series Specifications

General IconGeneral
BrandAPT
ModelLW39-25 Series
CategorySwitch
LanguageEnglish

Related product manuals