technical areaarea tecnica
INSERIMENTO CODICE D’ACCESSO 222
ruotare l’encoder per selezionare 234 e premere il tasto OK
MENU COMPLETO
0RETE
0. 2 RETE BUS
0. 2. 0 Rete Bus attuale Caldaia
Indicazione dispositivi connessi via BUS
0. 4 DISPLAY
0. 4. 0 Zona da impostare da dispay da 1 a 3 (nr) 1
0. 4. 1
Temporizzazione backlight da 1 a 10 minuti o
24h
0
0. 4. 2 Disattiva tasto
termoregolazione
0 = Tasto AUTO
attivo
1 = Tasto AUTO
diasattivato
0
2 PARAMETRI CALDAIA
2. 0 IMPOSTAZIONI GENERALI
2. 0. 0 Impostazione temperatura
sanitario
da 60 a 36 (°C) 45
regolabile dati Tasti 2
2. 2 IMPOSTAZIONI GENERALI
2. 2. 0 Lenta Accensione da 0 a 100 0
0 %
Valore massimo 100%
Valore minimo 0%
2.2.0 Livello Lenta Accensione
Vedi Tabella riepilogativa gas
2. 2. 2 < Non Disponibile >
2. 2. 4 Termoregolazione 0 = Assente
1 = Presente
0
E’ possibile attivare la termoregolazione premento il
tasto AUTO
2. 2. 5 Ritardo partenza in
riscaldamento
0= Disabilitato
1= 10 secondi
2= 90 secondi
3= 210 secondi
0
2. 2. 6 Con gurazione caldaie
convenzionali
da 0 a 5
0= Monotermica
camera aperta
0
RISERVATO AL SAT Solo in caso di sostituzione della scheda
elettronica
2. 2. 8 Versione Caldaia
NON MODIFICARE
da 0 a 5 0
RISERVATO AL SAT Solo in caso di sostituzione della scheda
elettronica
2. 2. 9 Settaggio potenza nominale
caldaia
RISERVATO AL SAT Solo in caso di sostituzione della scheda
elettronica
SERVICE CODE
Rotate encoder clockwise to select code 234 and press O
K
COMPLETE MENU
0 NETWORK
0. 2 BUS NETWORK
0. 2. 0 Network Presence Boiler
Indication of the devices connected via BUS.
0. 4 BOILER USER INTERFACE
0. 4. 0 Zone to be set by display from 1 to 3 (nr) 1
0. 4. 1 Backlight timing from 1 to 10
minutes or 24 hours
0
0. 4. 2 Thermoregulation button
deactivation
0 = Enabled AUTO
button
1= Disabled AUTO
button
0
2 BOILER PARAMETERS
2. 0 GENERAL
2. 0. 0
DHW Setpoint Temperature from 36 to 60 (°C)
Setting by DHW button 2
2. 2 BOILER GENERAL SETTINGS
2. 2. 0 Soft ignition from 0 to 100 0
0 %
Maximum value 100%
Minimum value 0%
2.2.0 Soft ignition
see Table summarising changes
2. 2. 2 < Not Available >
2. 2. 4 Termoregulation 0 = Absent
1 = Present
0
Termoregulation can be activated by pressing the
AUTO button.
2. 2. 5 Heating ignition delay 0 = Deactivated
1 = 10 seconds
2 = 90 seconds
3 = 210 seconds
0
2. 2. 6 Conventional boilers con g from 0 to 5
0= Mono Opern
Chamber
0
ONLY FOR SERVICE - To be used only in substitution P.C.B.
2. 2. 8 Boiler version
- NOT TO MODIFY
from 0 to 5 0
ONLY FOR SERVICE - To be used only in substitution P.C.B.
2. 2. 9 Set boiler heat power
ONLY FOR SERVICE - To be used only in substitution P.C.B.
menu
sotto-menu
parametro
descrizione range
impostazioni di
fabbrica
note
menu
sub-menu
parameter
description value
default
setings
notes