Chapter 3: Configuration and commissioning
2X-A Series Installation Manual 103
First zone indicator LED
The first zone indicator LED defines the zone number for the first LED (top left)
for an installed zone indicator board. The remaining zones for the corresponding
control panel follow sequentially, as shown in Table 49 below.
The initial zone range is as follows:
• Between 01 and 9960 for a 40-zone indicator board
• Between 01 and 9980 for a 20-zone indicator board
• Between 01 and 9976 for a 24-zone indicator board
Table 49: Zone LED indicator initial zones
Initial zone Remaining zones
-zone indicator board [1] 1 2 to 20
-zone indicator board [1] 200 201 to 239
-zone indicator board [2] 9976 9977 to 9999
[1] For large cabinet control panels.
[2] For small cabinet control panels.
Note: Ensure that the zone numbers selected are inside the zone range of the
control panel in networked mode or that the zone numbers are inside the range
of the zones repeated by the control panel.
Number of global zones
Note: This feature is not available if the initial zone is 0.
Configures the number of global zones available when the control panel is in
Networked mode.
Configuring the number of global zones helps to avoid zone overlap in
installations where zone numbering is configured to avoid sharing some zones
across the network. By configuring this setting, the same number of shared
zones is maintained after upgrading the control panel firmware to version 3.5 (or
later) and unexpected cross-panel activations are avoided.
Example:
If the number of global zones is 100 and the initial zone is 1, then a remote alarm
in zone 101 is reported as an alarm in the remote zone (because zone 101 is not
a global zone). However, if a remote alarm is reported in zone 90, the local
control panel enters into alarm (because zone 90 is a global zone).