Chapter 3: Configuration and commissioning
2X-A Series Installation Manual 75
Class B
Select Class B to configure your fire network class configuration (Class A or
Class B). The default setting is NO (Class A network configuration).
To change the network class settings:
1. Select Panel setup from the Main menu.
2. Select Firenet, and then select Class B.
3. Select YES (for Class B network) or NO (for Class A network).
4. Press F4 (Enter), and then press F1 (Back).
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.