Gree GMV6 DC Inverter VRF Units Service Manual
64
Parameter Code
Parameter Name
Remarks
27 Subcooler EEV
The displayed value is the integer value of the
actual value divided by 10.
28
Defrost temperature
Defrost temperature 1 is used.
29
Subcooler's liquid outlet temperature
30
Outlet temperature of accumulator
31
Oil return temperature
32
Inlet pipe temperature of the condenser
33
Outlet pipe temperature of the
condenser
Note:
If a parameter value is negative, LED3 circularly displays negative value code "nE" and the
numerical value every 1 second. For example, for 30, LED3 circularly displays nE for 1 second, and 30.
Discharge temperature and ambient temperature values are in four digits. The LED circularly
displays the left two digits and then the right two digits. For example, 01 and 15 indicate 115 degrees,
while nE, 00, and 28 indicate 28 degrees.
If a parameter is invalid on the unit, value "00" is displayed.
If there are two levels of menus on the master unit, you can press the SW4 back button to return to
the previous level. Press the SW4 query button again to exit query status.
If you do not press any button on the master unit in 5 minutes, the system will automatically exit the
current screen and the unit will resume displaying the current status.
4.2.4.3 n8 Indoor Unit Engineering SN Query
Introduction:
This function makes all indoor units display their SN respectively by performing an operation on the
outdoor unit, facilitating indoor unit address query.
Operations:
Press the SW1 up button and the SW2 down button to select indoor unit engineering SN query. The
master unit displays as follows:
LED1
LED2
LED3
Function Code Display status
Current
process/mode
Display status Current status Display status
n8
Blinks
00
Blinks
00
Blinks
Press the SW3 confirm button on the master unit to confirm the selection. The master unit displays
as follows, and other modules normally display the corresponding status:
LED1
LED2
LED3
Function Code Display status
Current
process/mode
Display status Current status Display status
n8
On
00
On
00
On
At this time, regardless of the current display status of all indoor unit wired controllers or display
panels, all of them switch to display the engineering number of the internal unit, without affecting the
setting and operation status of the indoor units and the outdoor unit.
Press the SW4 back button on the master unit to return to the upper operation level, but the indoor
units remains displaying the engineering numbers.