2
IMMERSION WELLS
WIRING
Ascent HydroStat can be installed on an existing immersion well already in the boiler or on a Hydrolevel Electro-Well™
(sold separately). The low water cut-off function is automatically activated when installed on an Electro-Well™.
IMPORTANT: The control will not provide low water cut-off protection when installed on a standard immersion well.
NOTE: Do not use heat-conducting grease.
Ascent HydroStat installed
with Hydrolevel Electro-Well™
Ascent HydroStat installed
with standard immersion well
IMPORTANT: For proper operation of the low water cut-off function, there must
be a minimum of ½" clearance between the copper well tube and any surface
within the boiler.
See Electro-Well models on page 15.
NOTE: When installed on a standard immersion well, the “LWCO Active” LED will
not illuminate.
IMPORTANT Make sure that the immersion well or Electro-Well
™
is installed in the boiler manufacturer’s designated temperature
limit control tapping.
NOTE: If installing an Electro-Well, pipe sealing compound should be used. Teflon tape is not recommended.
IMPORTANT Sensor must be inserted all the way into the well for proper operation.
CORRECT INCORRECT
NOTE: In the case of space restrictions, the Ascent HydroStat control may be mounted in a horizontal orientation without any loss of function. Hydrolevel
recommends vertical mounting, when possible, for proper orientation of LED display.