Page 8 of 16
The built-in proximity switch is indicated on the type
plate as product coding and wiring diagram.
For use in potentially explosive atmospheres, the devices must be connected to certified
intrinsically safe circuits.
For non-electrical part of device the requirements of the applicable standards EN ISO 80079-36:2016, EN ISO 80079-
37:2016 and EN 1127-1:2019 were considered by an ignition hazard assessment. The applicable requirements of
these standards have been met.
For the European Union the documentation has been filed with TÜV-Nord-Cert NB 0044 (see Declaration of
Conformity).
4 Technical data
The detailed technical information can be found in the documents in the Appendix, Chapter 12.
EU type examination certificates for the built-in inductive
proximity switch
Product code File number
PTB 99 ATEX 2219 X
IxxxxSN PTB 00 ATEX 2049 X
Electrical connection parameters
Max. supply voltage Umax = 16 V
Max. current Imax = 25 mA
Max. power Pmax = 64 mW
Max. capacity of proximity switch Ci max = 30 nF
Max. conductivity of proximity switch Li max = 100 μH
Recommended isolating switch amplifier ATEX SILx Namur
Switch contact
Code Ixxxx
KCD2-SOT-Ex1.LB (1-channel)
KCD2-SOT-Ex2 (2-channel)
x SIL2 Namur
Switch contact
Code IxxxxSN
KFD2-SH-EX1 (1-channel)
x SIL3 Namur with safety
function