2. Power Mode
E. Troubleshooting
Prior to electrical troubleshooting, confirm that the mechanical system properly functions; i.e., that the pushbar fully retracts all latches and
the door opens freely. See the table on page 13. Refer to applicable 6000 Series Exit Device product instruction sheet to correct mechanical
installation issues.
IMPORTANT:
* ALWAYS disconnect power before making any mechanical adjustments to the system.
Table 6 - Power Mode Troubleshooting
The pushbar does not move when 24V input is applied:
Check inputs to confirm proper voltage and wiring orientation (Figure 6 ElectroLynx Power Mode Installation).
Remove end cap from pushbar and confirm that LED is blinking steadily when power is applied. If not, refer to LED signaling.
NOTE:
When configured in Power Mode, power is released to lock the device (LED will not blink when power is released).
Confirm DIP switch position 3 is set to ON.
The pushbar does not fully retract or pushbar retracts completely and holds but does not open door:
* Verify mechanical installation and correct as necessary:
− Is excessive force required to depress the pushbar?
− Are latches fully clearing the strikes when mechanically cycled?
The pushbar retract and unlocks electrically but does not relock:
Physically disconnect power from pushbar and confirm that input is off.
*Check for mechanical interference (e.g., warped door, lack of shims, misalignment of pushbar, etc.).
Rail behaves abnormally (multiple cycles, clicking, delayed retraction, etc.):
Remove end cap from pushbar and confirm that LED is blinking steadily when power is applied. If not, refer to LED signaling.
NOTE:
When configured in Power Mode, power is released to lock the device (LED will not blink when power is released).
For applications using automatic operator(s): Door(s) fail to unlock before doors begin to open:
Adjust timing of operator to allow 900ms for the pushbar to fully retract.
“S” switch wiring: The design requires normally open functionality and the circuit is normally closed (or vice versa).
There is only a two-wire input for the “S” circuit. Normally open or normally closed configuration is set by toggling the DIP switches
on the controller bracket to the required position
For additional installation assistance, please contact 1-800-810-9473. When calling, please provide the following information to
improve our service (provide what you can):
Your name and contact number.
6000 Series Exit Device product type with options.
Location and identification of the affected opening (e.g., site, building, and door number).
Order Number (located on product box), if available.
Power supply manufacturer and rated output (i.e, voltage and current).
Method of operation (e.g., Power Mode).
The number of devices connected to the power supply.
Symptoms of problem (i.e., observed behavior).