3. Timer Mode
C. Adjustment
The 24 volt input is always energized and the system retracts when the
timer input circuit is closed.
When the timer circuit is closed utilizing a momentary switch, the
device retracts, remains retracted for a set duration, and releases.
The duration of retraction is set using an onboard timer setting (0 –
20 second timer adjustment).
The device retracts when timer circuit is closed using a maintain
switch and releases when circuit is reopened.
NOTE:
24V supply is constant in Timer Mode. The duration of retraction is
determined by whichever is longer: the maintain switch closure or
the onboard timer delay.
If more than a 20 second delay is necessary (exceeding the
maximum setting), an external timer delay relay is required (not
provided).
Refer to settings in Figure 20 for DIP Switch timer delay settings.
Figure 20: DIP Switch Settings
Timer Delay Settings
(Default = 5 Seconds (Sec))