6. Mount the door stop arm on the spline (see figure a), as close as possible to the stop
block (figure b). Fine-adjust if necessary with the screw on the stop block (figure c).
.
a b c
0°
SPTE
Auto-teach – automatically sets backcheck and latch
This procedure is performed by pushing the Teach button (LRN). There will be a 2
second delay before door starts.
Note: Before the teach procedure starts, make sure that the door has been properly
closed.
•If any of the parameters “Spring tension” (SPTE), “Closing force” (CLTQ)
and “Lock release” (DIP-switch No. 3 on auxiliary control board) are changed
after teaching, repeat teaching procedure.
•Operator can be taught with activation units and locks connected.
•The backcheck will be automatically adjusted to 10° and 1 second before
open position. The latch will be automatically adjusted to 10° and 1.5 seconds
before closed position.
10°/1 s
10°
1.5 s
LatchBackcheck
LRN
Warning! Remain clear of swing path of door,
as door may close rapidly. The door
has no safety during auto-learn cycle.
7. Close the door by turning the potentiometer SPTE to 0°.
Note: Activations are not accepted if SPTE is more than 0°.