14.5 O verhead Presence Detection (OPD) Monitoring (Level 4)
a Disconnect batteries if any.
b Disconnect the mains.
c Press the LEARN BUTTON (LRN) and keep it depressed.
d Connect the mains.
e Watch the ERROR LED.
3 s 3 s 3 s1 s
1 s
3 s
1 s
f Release the LEARN BUTTON after 4 flashes (LED is out).
g Identify the current monitoring
The ERROR LED flashes an amount of short flashes that correspond to the status number.
After a short pause the LED will repeat the status number and so on.
h Changing the status
If you push the LEARN BUTTON once, the status number will increase. When you have reached
the highest status number it will start at number one again.
Push the button until you get the requested monitoring status, 1 = OFF (default), 2 = ON
Disconnect the mains
Next time you connect the mains the operator will use the new status setting.
i Recommended settings for sensor SP34-M
Sensor Control unitInterface
Sensor
Interface
Control unit
Sensor dip switch settings
Dip 1 = ON
Dip 2-8 = OFF
Interface dip switch settings
Dip 1, 4 and 7 = OFF
Dip 2, 3, 5, 6 and 8 = ON
1005088-en-22.0Issue 2021-02-2460