12.1.5 Extension unit EXU-SA
This extension unit has inputs for door mounted sensors, which can give presence impulse on approach side
and/or presence detection on swing path side. Relay output for error indication or door indication is also integ-
rated. When the jumper for the relay is set to ‘Open door indication’, its activation will follow the Blanking LED.
Functions
8 9 101 2 3 4 5
NO
COM
NC
24 V DC
QTST
PDET
PIMP
GND
6 7
Monitoring of presence detection/DMPS.SS
Monitoring of presence impulse/DMPS.NS
No monitoring (both jumpers on)
Monitoring of presence detection and presence impulse
External error indication/KILL OUT/Lock
Opened/closed door indication
Ground
Remove strapping when connecting to terminals 2
and/or 3
Blanking potentiometer
(Adjust the potentiometer to avoid presence detection sensor to detect the wall.
Range 55 degrees - fully open / Max.)
Opened / closed door indication
Blanking LED
Door mounted sensors
2)
DMPS:
Relay 1: Presence im-
pulse (NC)
Relay 2: Presence detec-
tion (NC)
(-) 0 VDC Ground
(+) 24 VDC
Relay output (“External error, KILL OUT, Lock indication” or
“Open/closed door indication”, see above) 24 V, 1 A
Note! To make the dry relay output follow the electric lock output,
see group parameters 14, 15 and 16 plus pin jumper above.
Not to be used.
Blanking
MIN
Closed door
indication
MAX
Open door
indication
QTST = Sensor monitoring and reference for KILL (NC)
PDET = Presence detection (NC)
1)
PIMP = Presence impulse (NC)
1)
1)
If not used strap to “Ground”.
2)
Remove strapping from terminals 2 and/or 3.