12.4 Settings for double doors
Settings on the
Function
SecondaryPrimary
Common
XProgram selection
XOpening time
XClosing time
XHold open time
XClose / Continue to open when the door is obstructed
XPAG On/Off
XSOS On/Off
(X)*XLevel of Power assist
(X)*XExtended closing torque
XOPD/OPS Impulse or Mat Logic Impulse
XSelection of operating mode during operation on battery
power
Individual
XXLock/Unlock signal voltage
XXLocked without/with power
XXLock release Enable/Disable
XXOpen Delay Time
XXLock kick Enable/Disable
* For “Double egress doors”, these functions must be set separately for primary and secondary as
the arm systems as well as the air pressure may be different.
Note!
• Locks on the primary and secondary doors must be connected to the control unit (CU) on the
corresponding operator.
• Inner and outer impulses can be connected to either primary or secondary CU or both.
• The OPD/OPS is to be connected to the primary CU except for “Double egress”, where each
OPD/OPS must be connected to corresponding CU.
• Door leaf mounted sensors must always be connected to corresponding CU.