- 24 -
2.4.1.5 Control panel with Qc4002™ MkII
controller
General description Qc4002™ MkII control panel
A2 .......Qc4002™ MkII display
F10......Fuse
The fuse (10 A) trips when the current from
the battery to the engine control circuit
exceeds its setting. The fuse can be reset by
pushing the button.
S2 .......Emergency stop button
Push the button to stop the generator in case
of an emergency. When the button is
pressed, it must be unlocked, before the
generator can be restarted. The emergency
stop button can be secured in the locked
position with the key, to avoid unauthorized
use.
S11 .....Frequency selector switch (50 Hz/
60 Hz)
Allows to choose the frequency of the output
voltage: 50 Hz or 60 Hz.
S20......ON/OFF switch
Position O: No voltage is supplied to the
Qc4002™ MkII module, the generator will
not start.
Position I: Voltage is supplied to the
Qc4002™ MkII module, it is possible to
start up the generator.
X25 .....Connection block
Inside the cubicle. Allows customer
connections.
X30 .....Connector X30
Connector for communication with other
generators with Qc4002™ MkII when
paralleling, both in ALS and PMS mode. An
adapter can be plugged in. See page 84.
X40 .....Transformer Maintenance controls
connector
X41 .....Transformer Maintenance sensing
connector
X30
X2
N13
Q2
X41
X40
Qc4002
G
!
OK
LOG
0 I
S20
S11
50Hz 60Hz
F10
X30 X41X40
S2
X25S11 A2 S20 F10
Changing the output frequency is
only allowed when the unit has
stopped.
Refer to circuit diagram for the
correct connection.