Parameter overview (for correct values refer to controller)
Next paragraph shows the description of all customer level parameters, which can be accessed using password "2003".
In order to receive the default parameters for your unit, please contact Atlas Copco Service staff.
Protection setup
1001 Setpoint
-50% – 200.0%
1002 Delay
0.1 s – 100.0 s
1003 Output A
Not Used – Option dependent
1004 Output B
Not Used – Option dependent
1005 Enable
Off – On
1006 Failclass
Alarm (1) – Trip MB (6)
1031 Setpoint
50.0% – 200.0%
1032 Delay
0.1 s – 100.0 s
1033 Output A
Not Used – Option dependent
1034 Output B
Not Used – Option dependent
1035 Enable
Off – On
1036 Failclass
Alarm (1) – Trip MB (6)
1000 G -P> 1
1030 G I>1
1051 Setpoint
-50% – 200.0%
1052 Delay
0.1 s – 100.0 s
1053 Output A
Not Used – Option dependent
1054 Output B
Not Used – Option dependent
1055 Enable
Off – On
1056 Failclass
Alarm (1) – Trip MB (6)
1061 Setpoint
-50% – 200.0%
1062 Delay
0.1 s – 100.0 s
1063 Output A
Not Used – Option dependent
1064 Output B
Not Used – Option dependent
1065 Enable
Off – On
1066 Failclass
Alarm (1) – Trip MB (6)
1131 Setpoint
150.0% – 350.0%
1132 Delay
0.0 s – 100.0 s
1133 Output A
Not Used – Option dependent
1134 Output B
Not Used – Option dependent
1135 Enable
Off – On
1136 Failclass
Alarm (1) – Trip MB (6)
1141 Setpoint
150.0% – 350.0%
1142 Delay
0.0 s – 100.0 s
1143 Output A
Not Used – Option dependent
1144 Output B
Not Used – Option dependent
1145 Enable
Off – On
1146 Failclass
Alarm (1) – Trip MB (6)
1050 G I>3
1060 G I> 4
1130 G I>>1
1140 G I>>2
1151 Setpoint
100.0% – 120.0%
1152 Delay
0.1 s – 100.0 s
1153 Output A
Not Used – Option dependent
1154 Output B
Not Used – Option dependent
1155 Enable
Off – On
1156 Failclass
Alarm (1) – Trip MB (6)
1171 Setpoint
50.0% – 100.0%
1172 Delay
0.1 s – 100.0 s
1173 Output A
Not Used – Option dependent
1174 Output B
Not Used – Option dependent
1175 Enable
Off – On
1176 Failclass
Alarm (1) – Trip MB (6)
1150 G U>1
1170 G U<1
1191 Setpoint
50.0% – 100.0%
1192 Delay
0.1 s – 100.0 s
1193 Output A
Not Used – Option dependent
1194 Output B
Not Used – Option dependent
1195 Enable
Off – On
1196 Failclass
Alarm (1) – Trip MB (6)
1211 Setpoint
100.0% – 120.0%
1212 Delay
0.2 s – 100.0 s
1213 Output A
Not Used – Option dependent
1214 Output B
Not Used – Option dependent
1215 Enable
Off – On
1216 Failclass
Alarm (1) – Trip MB (6)
1190 G U<3
1210 G f>1
1231 Setpoint
100.0% – 120.0%
1232 Delay
0.2 s – 100.0 s
1233 Output A
Not Used – Option dependent
1234 Output B
Not Used – Option dependent
1235 Enable
Off – On
1236 Failclass
Alarm (1) – Trip MB (6)
1241 Setpoint
80.0% – 100.0%
1242 Delay
0.2 s – 100.0 s
1243 Output A
Not Used – Option dependent
1244 Output B
Not Used – Option dependent
1245 Enable
Off – On
1246 Failclass
Alarm (1) – Trip MB (6)
1230 G f>3
1240 G f<1