Table 1:
Cable types for dual pair Profinet cables
Application type CApplication type BApplication type ACable types
Dual pair data cableDual pair data cableDual pair data cableVersion
special applications (e.g. for con-
tinuous movement, vibration or
twisting)
flexible installation (e.g. for continu-
ous movement, vibration or twist-
ing after installation)
fixed installation, immobile after
installation
Type of installation
Cable parameter
"PROFINET type C""PROFINET type B""PROFINET type A"Designation (minimum)
AWG 22/.. 0.318 mm²AWG 22/7 0.318 mm²AWG 22/1 0.610 mm²
Cross section
depending on the application5.5 8.0 mmOuter cable diameter
depending on the application
1.4 ± 0.2 mm
Wire diameter
depending on the applicationGreen RAL6018Colour of shield
Pair 1: white, blue
Pair 2: yellow, orange
Colour of wire insulation
4Number of wires
Dual pair or star quadCable design
depending on the applicationAluminium foil + copper braidShield
Communication requirements
ISO/IEC 11801 Edition 2.0
IEC 61140-1
IEC 61156-6
(minimum device group 5)
ISO/IEC 11801 Edition 2.0
IEC 61140-1
IEC 61156-5
(minimum device group 5)
Applicable standards
20 ns/100 m
Delay
80 dB at 30 100 MHz
"Channel class-D" according to EN 50174-2
Coupling attenuation
Minimum cable spacing
The minimum spacing (according to IEC 61918) required between laying Profinet
cables and other cables must be respected.They are shown in the table below.
Table 2:
Minimum spacing for Profinet cables
Spacing to Profinet cable
Steel cutoff bridgeAluminium cutoff bridgeWithout or with non-metal
cutoff bridge
Signal transmission cable
0 mm0 mm0 mmFor example other Profinet cables, Profibus cables, data
cables for PCs, programming devices, shielded analogue
inputs
Power supply cables
50 mm100 mm200 mmUnshielded power supply cables
0 mm0 mm0 mmUnshielded power cables
Further references
Available Profinet recommendations, particularly planning, assembly and
commissioning guidelines of the PROFIBUS User Organisation (PNO)
(www.profibus.com) must be met.
2.7. Profinet conformance classes
To simply the application of Profinet, various conformance classes are defined which
specify required properties of the Profinet components and ensure their interoperability
by certifications.
The main properties of the conformance classes are shown in the table below:
10
Actuator controls
General information on Profinet AC 01.2/ACExC 01.2 Profinet