Table 27: Byte 32: SIL signals
DescriptionValuePrm-Text-Def GSD fileDesignation
(process representation)
Bit
Safe ESD (Emergency Shut Down) safety function of the
SIL sub-assembly is active.
1Safe ESD
Safe ESD
1)
0
No signal0
Safe STOP safety function of the SIL sub-assembly is
active.
1Safe STOP
Safe Stop
1)
1
No signal0
Collective signal
Warning: A SIL fault of the SIL sub-assembly has oc-
curred.
1SIL fault
SIL fault
1)
2
No signal0
A safety function of the SIL sub-assembly is active.1SIL function active
SIL function active
1)
3
No signal0
FQM Failsafe Active
FQM active
4
FQM Failsafe Init
FQM init.
5
FQM Failsafe Error
FQM fail safe fault
6
No signal (reserved)7
The safety function indications via communication interface are for information only and must not be used as part of a safety function.
The I/O signals of the SIL module must be used for this purpose.
1)
Byte 33 to byte 40: Reserve
The contents are reserved for future extensions.
4.2. Output data (process representation output)
The consumer (controller) can control the provider (actuator) via the process
representation output.
4.2.1. Process representation output arrangement
Information
To perform remote operations, the selector switch must be in position Remote
control (REMOTE).
Module definition
Module ID="ID_MODULE_ADI_OUT_0"
ModuleIdentNumber="0x00008100"
ModuleInfo CategoryRef=Output
Name TextId="Inputs"
InfoText TextId="Prozessabbild Output Daten"
Sub-module definition
VirtualSubmoduleItem ID="ID_SUBMOD_ADI_OUT_0"
SubmoduleIdentNumber="0x00002200"
API="0"
FixedInSubslots="2"
Name TextId="Outputs"
InfoText TextId="Prozessabbild Output Daten"
I/O data definition in sub-module
IOData IOPS_Length="1"
IOCS_Length="1"
Output Consistency="All items consistency">
30
Actuator controls
Description of the data interface AC 01.2/ACExC 01.2 Profinet