Causes and remedies
Possible causes and remedies:
●
I/O controller does not issue an operation command
●
I/O controller sends wrong operation command.
→ Check program of DCS
YesOperation via push button
of the local controls pos-
sible?
5.
Possible causes and remedies:
Faults such as torque, thermal or internal fault
→ Check logic board, motor control and motor.
No
6.2. Diagnostic
Various Profinet interface states can be checked via the menu Diagnostic M0022.
The <Information on Profinet> table shows the menus for the Profinet interface.
Table 39: Information on Profinet
Value and descriptionIndication on display
Manufacturer ID
Vendor ID M1834
Ident code
Ident code M1821
Manufacturer name
Vendor name M1822
Profinet device type
Profinet device type M1953
Profinet device name
Profinet dev. name M1856
IP address
IP address M1841
Subnet mask
Subnet mask M1849
Gateway
Gateway M1850
MAC address of Profinet module
MAC address module M1851
MAC address of Profinet port 1
MAC address port 1 M1852
MAC address of Profinet port 2
MAC address port 2 M1853
Firmware version of Profinet module
FW version module M1865
Device is currently used to exchange data (DataEx) – connection to I/O controller active
and valid data received by I/O controller
Channel 1 DataEx M1808
Activity of communication interface on channel/port 1 available – data blocks are detected
Channel 1 activity M1809
Activity of communication interface on channel/port 2 available – data blocks are detected
Channel 2 activity M1860
Network status
Network status M1818
Status of Profinet module or Profinet connection
Module status M1854
Configuration error of module
Config. error module M1855
The Profinet module is not available
Fieldbus mod. not avail. M1859
41
Actuator controls
AC 01.2/ACExC 01.2 Profinet Corrective action