Reading device specific process data (PZD)
Access is made via slot, subslot and index according to the following rule:
●
Slot = 0
●
Subslot = 1
●
Index = attribute "Object ID" for process data (PZD) of parameter list in appendix
If access is denied, one of the following fault indications is returned with the response
telegram:
Table 41:
CauseError
Code
Error
Class
Fault indication
An invalid index was accessed.011Access.Invalid In-
dex
The date length transmitted is invalid (read access)311Access type con-
flict
No write access permitted611Access.access
denied
Table 42: Device ID > Identification
ExplanationSetting valueDefaultAc-
cess
ParametersTypeID
Data length = 60 bytes
Device designation of actuator
controls
AC 01.2R
Device designation
S201164PRM
Information for actuator identific-
ation within the plant (e.g. KKS
designation - Power Plant Clas-
sification system)
_GERAETE-TAG_R/W
Device tag
S201165PRM
Project name of the plant
_PROJEKT_R/W
Project name
S201166PRM
Table 43: Device ID > Identification > Actuator controls
ExplanationSetting valueDefaultAc-
cess
ParametersTypeID
Data length = 80 bytes
Order number of controls
_ KOMMNR
STEUERUNG _
R
Order no. controls
S201760PRM
Serial number of controls
_ WERKNR
STEUERUNG _
R
Serial no. controls
S201762PRM
Wiring diagram
TPCR
Wiring diagram
S201764PRM
Date of manufacture of the actu-
ator controls
_DATE_PRODUC-
TION_
R
Date of manufacture
S202176PRM
Table 44: Device ID > Identification > Actuator
ExplanationSetting valueDefaultAc-
cess
ParametersTypeID
Data length = 60 bytes
Actuator order number
_ KOMMNR AN-
TRIEB _
R
Order no. actuator
S201761PRM
Actuator serial number
_ WERKNR AN-
TRIEB _
R
Serial no. actuator
S201763PRM
Actuator wiring diagram
TPAR
Wiring diag. actuator
S201765PRM
46
Actuator controls
Appendix AC 01.2/ACExC 01.2 Profinet