ExplanationSetting valueDefaultAccessParametersTypeID
Operation command
Min = 0R
Operation command
DrvCmd4144PZD
Max = 0xFFFFFFFF
Running OPEN
Min = 0R
Running OPEN
BOOL264PZD
Max = 1
Running CLOSE
Min = 0R
Running CLOSE
BOOL265PZD
Max = 1
Setpoint position reached
Min = 0R
Setpoint pos.reached
BOOL401PZD
Max = 1
Limit switch OPEN
Min = 0R
Limit switch OPEN
BOOL375PZD
Max = 1
Limit switch CLOSED
Min = 0R
Limit switch CLOSED
BOOL376PZD
Max = 1
Torque switch OPEN
Min = 0R
Torque sw. OPEN
BOOL459PZD
Max = 1
Torque switch CLOSED
Min = 0R
Torque sw. CLOSED
BOOL460PZD
Max = 1
Table 73: Diagnostic > Bluetooth
ExplanationSetting valueDefaultAc-
cess
ParametersTypeID
Data length = 62 bytes
Information for actuator identific-
ation within the plant (e.g. KKS
designation - Power Plant Clas-
sification system)
_GER-
AETE-
TAG_
R/W
Device tag
S201165PRM
Bluetooth address (BD_ADDR)
of controls
XX:XX:XX:XX:XX:XXR
Bluetooth address
S202188PRM
Activate/deactivate Buetooth in-
terface
0: Function not active
1R/W
Bluetooth
enum2591PRM
1: Function active
Table 74: Diagnostic > Position transm. potent.
ExplanationSetting valueDefaultAc-
cess
ParametersTypeID
Data length = 10 bytes
Low limit setting of potentiomet-
er signal range (monitoring the
potentiometer span)
Min = 0610R/W
Low limit Uspan
U162402PRM
Max = 1023
Current voltage level difference
of the potentiometer.
Min = 0R
Volt.level diff. potent.
U16928PZD
Max = 1023
Raw value in end position
OPEN
0R
Raw val. pos. OPEN
U16828PRM
65535
Raw value in end position
CLOSED
0R
Raw val. pos. CLOSED
U16829PRM
65535
Potentiometer raw value /mV
0R
Potent. raw value /mV
U16345PZD
5000 [mV]
Table 75: Diagnostic > Position transm. MWG
ExplanationSetting valueDefaultAc-
cess
ParametersTypeID
Data length =
Minimum stroke of MWG
Min = 00R
Minimum stroke
U162858PRM
Max = 0
Minimum stroke of MWG
Min = 6400064000R
Minimum stroke
U162859PRM
Max = 64000
61
Actuator controls
AC 01.2/ACExC 01.2 Profinet Appendix