10. Checklists
10.1. Commissioning checklist
Table 9: Commissioning checklist
1. Fail safe unit, actuator and actuator controls correctly wired?
2. Actuator limit and torque switching setting complete?
3. End positions of fail safe unit correctly set?
4. Safe function (depending on the configuration) checked in accordance with the proof
test checklists?
Yes
No
5. Commissioning of basic settings (actuator controls) performed in accordance with
the operation instructions?
= Executed
10.2. Proof test checklists
If the proof test is performed according to proof test checklists, the pertaining
NOTICES contained in the <Tests and maintenance> chapter have to be observed.
The test step sequence must be respected.
10.2.1. Safe ESD safety operation (Safe OPENING/CLOSING)
Proof test checklist for version or configuration:
Safe ESD function Safe CLOSING (Safe ESD in direction CLOSE)
Safe ESD function Safe OPENING (Safe ESD in direction OPEN)
Table 10: Proof test checklist
Configuration
Safe OPENING
(ESD in direction fail safe position OPEN)
Configuration
Safe CLOSING
(ESD in direction fail safe position CLOSED)
1. Actuator in end position CLOSED? 1. Actuator in end position OPEN?
2. Fail safe fault signal?
FS failure NC (NC contact) output = open
(FS ready signal)
2. Fail safe fault signal?
FS failure NC (NC contact) output = open
(FS ready signal)
3. ESD input signal set to 0 V (low)?
(execute operating time measurement)
3. ESD input signal set to 0 V (low)?
(execute operating time measurement)
Yes
No
Check reaction of fail safe unit:
FQM operates in direction OPEN? (start of operating
time measurement)
Yes
No
Check reaction of fail safe unit:
FQM operates in direction CLOSE? (start of operating
time measurement)
Yes
No
FQM reaches end position OPEN? (Operating time
measurement complete.)
Yes
No
FQM reaches end position CLOSED? (Operating time
measurement complete.)
Yes
No
FQM operating time corresponds to indications on
name plate for 90° swing angle or the configured op-
erating time?
Operating time [50 %/+ 100 %]
Yes
No
FQM operating time corresponds to indications on
name plate for 90° swing angle or the configured op-
erating time?
Operating time [50 %/+ 100 %]
Yes
No
Check FS module signal behaviour:
Fail safe fault signal?
FS failure NC (NC contact) output = close
(FS fault signal)
Yes
No
Check FS module signal behaviour:
Fail safe fault signal?
FS failure NC (NC contact) output = close
(FS fault signal)
4. ESD input signal set to +24 V (high)? Start of time
measurement.
4. ESD input signal set to +24 V (high)? Start of time
measurement.
33
with non safety-related actuators Checklists